WSP240/I/TT (Mains, Type 1 & 2)

Single phase Type 1 and 2 tested (BS EN 61643) surge protector for use primarily on mains power distribution systems to protect connected equipment from transient overvoltages.

Designed for use at the boundaries of LPZ 0a to LPZ 2 as part of a coordianted SPD system (BS EN 62305), this type of protection is usually used for equipotential bonding in structures that have a Lightning Protection System (LPS) fitted, at the point cables enter the structure (LPZ 0a or b to LPZ 1 boundary).

Features and Benefits:

  • Repeated protection in lightning intense environments.
  • Per-phase remote signalling contacts allow surge protection status to be monitored via a building management system.
  • Thermal disconnect for safe disconnection from abnormal or faulty supplies.
TypeNominal VOperating V RangeMax. Current RatingMax. Surge Current 10/350μsNominal Surge Current 8/20μsMax. Surge Current 8/20μsLet-through VLocationPart Number
TypeMains, Type 1 & 2Nominal V240Operating V Range275 Max (L-N)Max. Current RatingN/A or 125A (config dependant)Max. Surge Current 10/350μs25kA (L-N); 50kA, (N-PE)Nominal Surge Current 8/20μs25kAMax. Surge Current 8/20μs40kA (L-N); 40kA, (N-PE)Let-through V<1.2kV @ IimpLocationLPZ 0-1 or 1-2Part NumberWSP240/I/TT

Tested: BS EN 61643-11