TypeC.S.A. (sqmm)Stranding No. x Ø (mm)Nominal Ø (mm)Maximum Resistance @ 20C Ω/kmWeight per Metre (kg)Part Number
TypeSoft DrawnC.S.A. (sqmm)6Stranding No. x Ø (mm)7 x 1.04Nominal Ø (mm)3.12Maximum Resistance @ 20C Ω/km3.080Weight per Metre (kg)0.05Part NumberCBS 006
TypeSoft DrawnC.S.A. (sqmm)10Stranding No. x Ø (mm)7 x 1.35Nominal Ø (mm)4.05Maximum Resistance @ 20C Ω/km1.830Weight per Metre (kg)0.09Part NumberCBS 010
TypeSoft DrawnC.S.A. (sqmm)16Stranding No. x Ø (mm)7 x 1.70Nominal Ø (mm)5.10Maximum Resistance @ 20C Ω/km1.150Weight per Metre (kg)0.15Part NumberCBS 016
TypeSoft DrawnC.S.A. (sqmm)25Stranding No. x Ø (mm)7 x 2.14Nominal Ø (mm)6.42Maximum Resistance @ 20C Ω/km0.727Weight per Metre (kg)0.23Part NumberCBS 025
TypeSoft DrawnC.S.A. (sqmm)35Stranding No. x Ø (mm)7 x 2.52Nominal Ø (mm)7.56Maximum Resistance @ 20C Ω/km0.524Weight per Metre (kg)0.32Part NumberCBS 035
TypeSoft DrawnC.S.A. (sqmm)50Stranding No. x Ø (mm)19 x 1.78Nominal Ø (mm)8.90Maximum Resistance @ 20C Ω/km0.387Weight per Metre (kg)0.43Part NumberCBS 050
TypeSoft DrawnC.S.A. (sqmm)70Stranding No. x Ø (mm)19 x 2.14Nominal Ø (mm)10.70Maximum Resistance @ 20C Ω/km0.268Weight per Metre (kg)0.62Part NumberCBS 070
TypeSoft DrawnC.S.A. (sqmm)95Stranding No. x Ø (mm)19 x 2.52Nominal Ø (mm)12.60Maximum Resistance @ 20C Ω/km0.193Weight per Metre (kg)0.86Part NumberCBS 095
TypeSoft DrawnC.S.A. (sqmm)120Stranding No. x Ø (mm)37 x 2.03Nominal Ø (mm)14.21Maximum Resistance @ 20C Ω/km0.153Weight per Metre (kg)1.09Part NumberCBS 120
TypeSoft DrawnC.S.A. (sqmm)150Stranding No. x Ø (mm)37 x 2.25Nominal Ø (mm)15.75Maximum Resistance @ 20C Ω/km0.124Weight per Metre (kg)1.33Part NumberCBS 150
TypeSoft DrawnC.S.A. (sqmm)185Stranding No. x Ø (mm)37 x 2.52Nominal Ø (mm)17.64Maximum Resistance @ 20C Ω/km0.099Weight per Metre (kg)1.67Part NumberCBS 185
TypeSoft DrawnC.S.A. (sqmm)240Stranding No. x Ø (mm)61 x 2.25Nominal Ø (mm)20.25Maximum Resistance @ 20C Ω/km0.075Weight per Metre (kg)2.20Part NumberCBS 240
TypeSoft DrawnC.S.A. (sqmm)300Stranding No. x Ø (mm)61 x 2.52Nominal Ø (mm)22.68Maximum Resistance @ 20C Ω/km0.060Weight per Metre (kg)2.76Part NumberCBS 300
TypeSoft DrawnC.S.A. (sqmm)400Stranding No. x Ø (mm)61 x 2.85Nominal Ø (mm)25.65Maximum Resistance @ 20C Ω/km0.047Weight per Metre (kg)3.53Part NumberCBS 400
TypeHard DrawnC.S.A. (sqmm)35Stranding No. x Ø (mm)7 x 2.52Nominal Ø (mm)7.56Maximum Resistance @ 20C Ω/km0.540Weight per Metre (kg)0.32Part NumberCHS 035
TypeHard DrawnC.S.A. (sqmm)50Stranding No. x Ø (mm)7 x 3.00Nominal Ø (mm)8.90Maximum Resistance @ 20C Ω/km0.399Weight per Metre (kg)0.43Part NumberCHS 050
TypeHard DrawnC.S.A. (sqmm)70Stranding No. x Ø (mm)7 x 3.55Nominal Ø (mm)10.70Maximum Resistance @ 20C Ω/km0.276Weight per Metre (kg)0.62Part NumberCHS 070
TypeHard DrawnC.S.A. (sqmm)95Stranding No. x Ø (mm)37 x 1.78Nominal Ø (mm)12.60Maximum Resistance @ 20C Ω/km0.199Weight per Metre (kg)0.86Part NumberCHS 095

Material: Copper to BS EN 60228:2005.