| |+44 (0) 115 927 1721

WSP135/10FM

The WSP135-10FM Wallis data line surge protector
Wiring diagram of a WSP135-10FM data line surge protector

High-frequency protection range designed for equipment connected to an aerial system by means of coaxial cables. Special gas discharge tubes with maximum discharge current (Imax) of 10kA (8/20μs) ensure reliable protection of receiving and transmitting systems even against a lightning stroke nearby.

A. N. Wallis offer a wide range of coaxial protectors for various connector types and transmission power grades enabling use in many applications. These coaxial protectors are recommended for use in the Lightning Protection Zones Concept at the boundaries of LPZ 0A(B)-1 and higher according to EN 62305.

Maximum Continuous Operating Voltage (Uc)Nominal Current (In)Max Transmission PowerInsertion LossReturn LossCharacteristic ImpedancePart Number
Maximum Continuous Operating Voltage (Uc)135VNominal Current (In)5AMax Transmission Power50WInsertion Loss<0.2dBReturn Loss>20dBCharacteristic Impedance50ΩPart NumberWSP135/10FM

.

Get In Touch

Get In Touch
Interested In:
Address

Get In Touch
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.