| |+44 (0) 115 927 1721

WSP25/T1

An image of the Wallis WSP25-T1
A wiring diagram of the A.N. Wallis surge protection device WSP25/T1

The WSP25/T1 surge protection device is configured in a 2+0 configuration (CT1 according to BS 7671), allowing for installation in TN-S and TN-C-S earthing systems. This configuration is not suitable for use with a TT earthing system.

This surge protection device is designed for use at the boundary of LPZ 0 to LPZ 1 in structures of LPL III and LPL IV (Class III and IV Lightning Protection Systems) as a Type 1 lightning arrester. The WSP25/T1 surge protection device is also Type 2 and Type 3 tested for use in sub-distribution boards and local equipment protection.

Earth TypeNominal Operating Voltage, L to PE (Un)Maximum Continuous Operating Voltage (Uc)Maximum Discharge Current, 8/20μs (Imax)Total Discharge Current, 10/350μsTotal Discharge Current, 8/20μsNominal Discharge Current, Class II, 8/20μs (In)Temporary Overvoltage, 5s (Ut)Temporary Overvoltage, 120min (Ut)Part Number
Earth TypeTN-S; TN-C-SNominal Operating Voltage, L to PE (Un)230V~Maximum Continuous Operating Voltage (Uc)275V~Maximum Discharge Current, 8/20μs (Imax)50kATotal Discharge Current, 10/350μs25kATotal Discharge Current, 8/20μs100kANominal Discharge Current, Class II, 8/20μs (In)25kATemporary Overvoltage, 5s (Ut)337VTemporary Overvoltage, 120min (Ut)440VPart NumberWSP25/T1

.

Get In Touch

Get In Touch
Interested In:
Address

Get In Touch
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.