WSP50/T1

An image of the Wallis WSP50-T1 surge protection device
A wiring diagram of the Wallis WSP50/T1

The WSP50/T1 surge protection device is configured in a 4+0 configuration (CT1 according to BS 7671), allowing for installation in TN-S and TN-C-S earthing systems. This configuration is not suitable for use with a TT earthing system.

This surge protection device is designed for use at the boundary of LPZ 0 to LPZ 1 in structures of LPL III and LPL IV (Class III and IV Lightning Protection Systems) as a Type 1 lightning arrester. The WSP50/T1 surge protection device is also Type 2 and Type 3 tested for use in sub-distribution boards and local equipment protection.

Earth TypeNominal Operating Voltage L to PE (Un)Maximum Continuous Operating Voltage (Uc)Maximum Discharge Current 8/20μs (Imax)Total Discharge Current 10/350μsTotal Discharge Current 8/20μsNominal Discharge Current, Class II, 8/20μs (In)Temporary Overvoltage, 5s (Ut)Temporary Overvoltage, 120min (Ut)Part Number
Earth TypeTN-S; TN-C-SNominal Operating Voltage L to PE (Un)230V~Maximum Continuous Operating Voltage (Uc)275V~Maximum Discharge Current 8/20μs (Imax)50kATotal Discharge Current 10/350μs50kATotal Discharge Current 8/20μs200kANominal Discharge Current, Class II, 8/20μs (In)25kATemporary Overvoltage, 5s (Ut)337VTemporary Overvoltage, 120min (Ut)440VPart NumberWSP50/T1

.